PML-AVF2-7N, Multi Meter, 12-24 VDC Supply, Input - Current: 0-5A, Volts: 0-600V, Freq: 2-400Hz
PML-AVF2-7N, Multi Meter, 12-24 VDC Supply, Input - Current: 0-5A, Volts: 0-600V, Freq: 2-400Hz
FMX PML Series Multi Meter, 72x72mm, Negative Backlit LCD, 12-24 VDC Supply Input, Measurement Input - Current: 0-5A (30VAC/60VDC), Voltage: 0-600V CATII, Frequency: 2-400Hz (10-600VAC) , 2 outputs programmable for Discrete (34VDC, 0.5A max) or Analog (4-20mA)
Quantity Pricing
Specifications
FMX PML Series Multi Meter, 72x72mm, Negative Backlit LCD, 12-24 VDC Supply Input, Measurement Input - Current: 0-5A (30VAC/60VDC), Voltage: 0-600V CATII, Frequency: 2-400Hz (10-600VAC) , 2 outputs programmable for Discrete (34VDC, 0.5A max) or Analog (4-20mA)
- 72x72mm Panel Meter
- UL Type 4 Indoor/Outdoor Protection
- Each output can be configured for discrete (34VDC, 0.5mA max) or analog (4-20mA) signals
- User adjustable backlight colors: green, red, and white
- Wide viewing angle
- Easily program with free PML Series Configurator
- Plug and Play, no need for special drivers
General Specifications
| Power Supply | |
| Nominal Input | 12-24VAC/DC ±10% |
| Max. Power | 1.6W |
| Supply Frequency | DC or 50 - 400Hz |
| Display | |
| Number of programmable starburst digits | 4 |
| Digit height | 0.47” (12mm) |
| Bar Graph Segments | 40 |
| Digit height of annunciator | 0.23” (6mm) |
| Number of annunciator digits | 4 |
| Backlight Colors | Red, Green, White |
| Display Update Frequency | 0.08 - 21 sec. |
| Viewing angle | +/- 70° |
| Digital Outputs | |
| Max Voltage | 34VDC |
| Min Voltage | 3.3VDC |
| Max Current | 500mA |
| Min Current | 0.1mA |
| Analog Outputs | |
| Output | 4-20mA |
| Accuracy | 0.50% |
| Resolution | 0.02mA |
| Environmental | |
| Temperature Operating | 14 to 140°F (-10 to 60°C) |
| Temperature Storage | 40 to 158°F (-40 to 70°C) |
| Altitude | 6562ft (2000 meters) |
| Relative Continuous Humidity | 0-85% |
| Pollution Degree | 2 |
| Rating | UL Type 4, 12, IP65 |
| Certification | UL, CE, RoHS, IEC 61010-1 |
| Connections | |
| Wire Type | Solid or Stranded |
| Wire Strip Length | 0.26” to 0.28” |
| Wire Gauge | 18AWG to 12AWG |
| Torque | 4.42 to 5.31 in-lb |
Meter Specifications
| Amp Mode | |
| Input Range | 0-5A; 30VAC/60VDC |
| Max Measurement using CT | 1000A (AC) 10,000A (AVF Meter) |
| Minimum CT Power Rating | 1 VA |
| Input Current Frequency | DC or 30 - 400Hz |
| Display Modes | Average DC or RMS |
| Isolation | 2.1KVAC for 1 min |
| Impedance | 2mΩ |
| Accuracy | 1% |
| Resolution | 2.4mA |
| Sample Rate | 62KHz |
| Voltage Input Isolation | 600VAC/DC |
| Current Input Isolation | 2 KV VAC/DC |
| Volt Mode | |
| Input Range | 0-600V (AC/DC) |
| Measurement category | CATII |
| Max overvoltage rating | 800V |
| Input Current Frequency | DC or 30 - 400Hz |
| Display Modes | Average DC or RMS |
| Impedance | 1.5MΩ |
| Accuracy | 1% |
| Resolution | 10mV |
| Sample Rate | 62KHz |
| Voltage Input Isolation | 600VAC/DC |
| Current Input Isolation | 2 KV VAC/DC |
| Frequency Mode | |
| Input Range | 2-400Hz; 10-600V |
| Measurement category | CATII |
| Impedance | 1.5MΩ |
| Accuracy | 0.10% |
| Resolution | 0.1Hz |
| Sample Rate | 62KHz |
| Voltage Input Isolation | 600VAC/DC |
| Current Input Isolation | 2 KV VAC/DC |
Resources
Application Notes
| Title | Summary | Related Links |
|---|---|---|
| AN-PML-001 PML Configurator Software Installation Guide | FMX PML Configurator software allows you to program and download ... | |
| AN-PML-002 Program the PML Panel Meter | How to Program the Panel Meter ... | |
| AN-PML-003 Measuring Voltage with a PML-VM2 Volt Meter | The PML-VM2 volt meter can measure both AC and DC voltages. ... | |
| AN-PML-004 PML-FM2 Frequency Meter | Measure Frequency with a PML-FM2 Frequency Meter ... | |
| AN-PML-005 Measurement of Voltage and Current | Measurement of Voltage and Current in a DC Load Bank Application ... | |
| AN-PML-006 Current Sensing with a PML-AM2 Amp Meter | The PML-AM2 amp meter can measure both AC and DC ... | |
| AN-PML-007 Silo Volume Application | Silo Volume Application Instructions... | |
| AN-TD2-010 Using a Panel Meter with TD200 | How to use a panel meter and potentiometer to provide external speed display and control with the TD200 | |
| AN-TD4-013 Using a Panel Meter with TD400 | How to use a panel meter and potentiometer to provide external speed display and control with the TD400 |