UTS800N-PX1-400, MCCB, 35KA, 3 pole, trip unit with Power Meter, Earth Leakage Protection, RS-485 Communication, 160-400A thermal range, 800-6000A magnetic range
UTS800N-PX1-400, MCCB, 35KA, 3 pole, trip unit with Power Meter, Earth Leakage Protection, RS-485 Communication, 160-400A thermal range, 800-6000A magnetic range
LS Electric Susol UT Series MCCB, UL489, 800A Frame, 35KA Interrupt Capacity, 3 pole, Line-side and Load-side lugs, Adjustable trip unit with Power Meter, AC/DC 100-250V 60Hz trip unit power, Earth Leakage Protection, RS-485 Communication, 160-400A thermal adjustable range, 800-6000A magnetic adjustable range. This item is special order and non-cancellable, non-returnable.
Specifications
LS Electric Susol UT Series MCCB, UL489, 800A Frame, 35KA Interrupt Capacity, 3 pole, Line-side and Load-side lugs, Adjustable trip unit with Power Meter, AC/DC 100-250V 60Hz trip unit power, Earth Leakage Protection, RS-485 Communication, 160-400A thermal adjustable range, 800-6000A magnetic adjustable range. This item is special order and non-cancellable, non-returnable.
- UL489 Listed MCCB for branch circuit protection
- New 100 amp frame with 2 or 3 pole options
- Digital trip unit for 800 and 1200 amp frames
- Multiple breaking capacity choices
- Optimal overload protection
- 600VAC maximum rated operational voltage
- UL File #E231289
Accessories
- Internal electrical auxiliaries (auxiliaries, alarms)
- Through-the-door rotary disconnect handles
- Flange-mount disconnect handles
- Locking devices
General Specifications
| Frame Size (AF) | 800 |
| Rated Amps | 400A |
| Number of Poles | 3 |
| Wire/Cable Size | AWG 3/0 - 400kcmil (3 conductor) |
| Rated Operational Voltage | 600VAC |
| UL Interrupting Rating | N (low) |
| 240VAC (50/60Hz) | 65kA |
| 480VAC (50/60Hz) | 35kA |
| 600VAC (50/60Hz) | 18kA |
| Mechanical Life (operations) | 3,000 |
| Electrical Life (operations) @600VAC | 500 |
| Trip Unit with Power Meter | Adjustable |
| Thermal Adjustable Range | 200 - 400A |
| Magnetic Adjustable Range | 800 - 6000A |
| Earth Leakage Protection | Yes (Except Residual Current) |
| Communication | RS-485 |
| Power Trip Unit | 100 - 250VAC/DC |
| Standards | UL 489 File No. E231289 |
| Dimensions | 12.88"H x 8.27"W x 6.14"D |
| Weight | 31.35lbs. |