UTS1200N-AX1-800, MCCB, 35KA, 3 pole, trip unit with Ammeter, Earth Leakage Protection, RS-485 Communication, 400-800A thermal range, 1600-12000A magnetic range

UTS1200N-AX1-800, MCCB, 35KA, 3 pole, trip unit with Ammeter, Earth Leakage Protection, RS-485 Communication, 400-800A thermal range, 1600-12000A magnetic range

LS Electric Susol UT Series MCCB, UL489, 1200A Frame, 35KA Interrupt Capacity, 3 pole, Line-side and Load-side lugs, Adjustable trip unit with Ammeter, AC/DC 100-250V 60Hz trip unit power, Earth Leakage Protection, RS-485 Communication, 400-800A thermal adjustable range, 1600-12000A magnetic adjustable range. This item is special order and non-cancellable, non-returnable.

Item: UTS1200N-AX1-800
(0) No Reviews yet
Weight: 40.28 lbs.
Made in: Korea (the Republic of)
$4,319.20
Lead Time Item
SKU:UTS1200N-AX1-800

Special Order Item: Call for lead times. Non-cancelable, Non-returnable.

Specifications

LS Electric Susol UT Series MCCB, UL489, 1200A Frame, 35KA Interrupt Capacity, 3 pole, Line-side and Load-side lugs, Adjustable trip unit with Ammeter, AC/DC 100-250V 60Hz trip unit power, Earth Leakage Protection, RS-485 Communication, 400-800A thermal adjustable range, 1600-12000A magnetic adjustable range. This item is special order and non-cancellable, non-returnable.

  • UL489 Listed MCCB for branch circuit protection
  • New 100 amp frame with 2 or 3 pole options
  • Digital trip unit for 800 and 1200 amp frames
  • Multiple breaking capacity choices
  • Optimal overload protection
  • 600VAC maximum rated operational voltage
  • UL File #E231289

Accessories
  • Internal electrical auxiliaries (auxiliaries, alarms)
  • Through-the-door rotary disconnect handles
  • Flange-mount disconnect handles
  • Locking devices

GENERAL SPECIFICATIONS

Frame Size (AF)1200A
Rated Amps800A
Number of Poles3
Wire/Cable SizeAWG 3/0 - 500kcmil (4 conductor)
Rated Operational Voltage600VAC
UL Interrupting RatingN (low)
240VAC (50/60Hz)50kA
480VAC (50/60Hz)35kA
600VAC (50/60Hz)18kA
Mechanical Life (operations)2,000
Electrical Life (operations) @600VAC500
Trip Unit with AmmeterAdjustable
Thermal Adjustable Range400 - 800A
Magnetic Adjustable Range1600 - 12,000A
Power Trip Unit100 - 250VAC/DC
Earth Leakage ProtectionYes (Except Residual Current)
CommunicationRS-485
StandardsUL 489
File No. E231289
Dimensions16.26"H x 8.27"W x 6.14"D
Weight40.28lbs.