MMS-63H-17A, MMS, 11 - 17A, DIN Rail Mount, IP20

MMS-63H-17A, MMS, 11 - 17A, DIN Rail Mount, IP20
LS Electric Manual Motor Starter, 11 - 17A, 690V Maximum Voltage, 50 kA Interrupting, Manual On / Off Control with Lockout, DIN Rail Mount Enclosure, IP20
Item: MMS-63H-17A
Weight: 2.3 lbs.
Made in: Korea (the Republic of)
$180.60
SKU:MMS-63H-17A
Specifications
LS Electric Manual Motor Starter, 11 - 17A, 690V Maximum Voltage, 50 kA Interrupting, Manual On / Off Control with Lockout, DIN Rail Mount Enclosure, IP20
- Class 10 thermal overload protection
- Lockable handle (OFF position)
- Trip test feature
- Phase loss protection
- Complies with IEC 60947-2 and IEC 60947-4-1 UL508 (Manual motor controller) UL508 (Combination motor controller starter) CSA C22.2 NO. 14 GB14048
GENERAL SPECIFICATIONS
Number of Poles | 3 |
Rated Operational Voltage (Ue) | Up to 690V |
Rated Frequency | 50/60Hz |
Rated Insulation Voltage (Ui) | 690V |
Rated Impulse Voltage (Uimp) | 6kV |
Utilization Category | IEC 60 947-2 (Breaker) : Cat. A IEC 60947-4 (Motor Starter): AC3 |
Mechanical Endurance (Operating) | 50,000 |
Electrical Endurance (Cycles) | 25,000 |
Maximum Operations per hour | 25 |
Resistance to Shock | 25g |
Resistance to Vibration | 5 - 150Hz |
Overload Protection | Yes |
Phase Failure Function | Yes |
Trip Test Function | Yes |
Thermal Overload Protection | Class 10 |
Thermal Adjustable Range | 11 to 17A |
Short Circuit Current Rating (SCCR) | 100kA at 240V 50kA at 480V 10kA at 600V |
Terminal Capacity | 1 or 2 conductor 18 to 4 AWG |
Terminal Torque | 26 to 39lb-in. ( 3 to 4.5 Nm) |
Storage Temperature | -58° to 176°F (-50 to 80°C) |
Operating Temperature | -4° to 140°F (-20° to 60°C) |
Degree of Protection | IP20 |
Starter Dimensions | 5.7"H X 2.2"W X 5.5"D (144.6 x 55 x 140mm) |
Starter Weight | 2.2 lbs. (1000g) |
Standards | UL508 File# E252942; CSA C22.2 IEC 60947-2 and IEC 60947-4-1 |
UL HP RATINGS
Single Phase | 115V - 1HP 230V - 3HP |
Three Phase | 200V - 3HP 230V - 5HP 460V - 10HP 575V - 15HP |