CRM-2T-UNI, Star/Delta Motor Start Timer, DIN Rail Mount
Star/Delta Motor Start Timer, Rotary Selector Switches, DIN Rail Mount, Star: 0.1 Seconds to 100 Days, Star to Delta: 0.1 to 1 second, 16A SPDT, Universal Coil Voltage 12 - 240 VAC/VDC, with LED
Item: CRM-2T-UNI
Weight: 0.3 lbs.
Made in: Czechia
$67.90
SKU:CRM-2T-UNI
Specifications
Star/Delta Motor Start Timer, Rotary Selector Switches, DIN Rail Mount, Star: 0.1 Seconds to 100 Days, Star to Delta: 0.1 to 1 second, 16A SPDT, Universal Coil Voltage 12 - 240 VAC/VDC, with LED
- Universal voltage (12-240 VAC/DC)
- Max power consumption, 3VA, 1.7W
- Two timer ranges; Star: 0.1 second to 100 days. Star to Delta: 0.1 to 1 second
- Slim DIN-rail mount, saves panel space
- LED status indicators
- Standard single module width
- Operating Temperature: -20 to 55°C
| Available Timing Functions |
|---|
| 25: Star-Delta Start Relay |
GENERAL SPECIFICATIONS
| Input Voltage | 12-240 VAC/DC |
| Input Voltage Tolerance | +10%; -15% |
| Consumption | 0.7 - 3 VA (AC) 0.5 - 1.7 W (DC) |
| Contact Rating : DPDT | 16A / 250VAC 16A / 24VDC |
| Breaking Capacity | 4000VA /AC1 384W / DC |
| Inrush Current | 30A /<3s |
| Switching Voltage | 250VAC / 24VDC |
| Min. Breaking Cap. DC | 500mW |
| Life | Mechanical: 30,000,000 operations Full Load (AC1) : 70,000 operations |
| Time Deviation | Mechanical Setting 5% |
| Repeat Accuracy | Set Value Stability 0.2% |
| Temperature Coefficient | at 68°F (20°C) 0.01% |
| Reset Time | Max. 150ms |
| Max Wire Size | 2 X 16 AWG 1 X 14 AWG |
| Protection | Front Panel: IP40 Terminals : IP20 |
| Ambient Temperature | Operating: -4 to 131°F (-20 to 55°C) Storage: -22 to 158°F (-30 to 70°C) |
| Standards | EN61812-1, EN61010-1 |
Application Notes
| Title | Summary | Related Links |
|---|---|---|
| AN-TMR-025 Star-Delta Start Relay | This video depicts the timing operation of the Star-Delta Start Relay function.. |