IOL-25S-010, Thermal Overload, 3 Pole, 7-10A
IOL-25S-010, Thermal Overload, 3 Pole, 7-10A
FMX Bimetallic Thermal Overload Relay, 3 Pole, 7-10A Current Range, Class 10, Screw Clamp Terminal, (compatible with ICxxx-09S to ICxxx-40S, ICxxxN-09S to ICxxxN-18S Contactors)
Item: IOL-25S-010
Weight: 0.4 lbs.
Made in: Brazil
$24.00
SKU:IOL-25S-010
Specifications
FMX Bimetallic Thermal Overload Relay, 3 Pole, 7-10A Current Range, Class 10, Screw Clamp Terminal, (compatible with ICxxx-09S to ICxxx-40S, ICxxxN-09S to ICxxxN-18S Contactors)
- Trip ranges from 0.28A to 420A
- Separate mount adapter available (through IOL-105S)
- Ambient compensated -4 to 140 °F (-20 to 60°C)
- Selectable RESET button (auto or manual)
- Differential current / phase loss protection
- Isolated 1 N.O. and 1 N.C. auxiliary contacts
- Trip class 10
- UL and CE Certified
- 1 year warranty
General Specifications
| Number of Poles | 3 |
| Rated Operation & Insulation Voltage | IEC 60947-4-1 690[V]; UL; CSA 600[V] |
| Rated Impulse Voltage [kV] | 6 |
| Tripping Class | 10 |
| Phase Failure Sensitivity | YES |
| Current | Direct: YES Alternating [Hz] Up to 400 |
| Ambient Temperature | Storage: -58 to 176 °F (-50 to 80°C) Operating: -4 to 158°F (-20 to 70°C) |
| Pollution Degree | 3 |
| Current Heat Loss [W] | 3 |
| Weight [lb] | 0.32 |
| Shock Resistance (IEC 60068-2-27; 1/2 Sine Wave) [g/ms] | 10/11 |
| Standards | IEC 60947-1 / 60947-4-1, UL 508; CSA C.22.2/14; VDE 0660/102 |
| Power Terminals IP Rating | IP10 |
| Main Terminals Capacity | Cross/Slotted Combination |
| Stranded / Solid (UL/CSA); 75°C, Cu Only [AWG] | 14 - 6 |
| Tightening Torque [lb-in] | 20 |