IC330-25S-00-AC480, Contactor, 25A, 3 Pole, Coil: 400-415/480VAC

FMX Contactor, 25A, 3 Pole, 600V, Screw Clamp Terminals, Coil: 400-415/480VAC, 50/60Hz

Weight: 0.8 lbs.Made in: Brazil

IC330-25S-00-AC480, Contactor, 25A, 3 Pole, Coil: 400-415/480VAC

FMX Contactor, 25A, 3 Pole, 600V, Screw Clamp Terminals, Coil: 400-415/480VAC, 50/60Hz

Weight: 0.8 lbs.Made in: Brazil
In Stock
$37.30
QuantityPrice

Orders up to 6PM ET Ship same day!

In Stock

Specifications

FMX Contactor, 25A, 3 Pole, 600V, Screw Clamp Terminals, Coil: 400-415/480VAC, 50/60Hz

  • 3/4HP to 75HP
  • DIN-rail mountable up to 105A frame
  • UL508 Listed
  • UL and CE Certified
  • IEC 60947
  • 1 year warranty

UL HP Ratings (AC3 Motor Load)

Single Phase
115V2HP (24A)
230V5HP (28A)
Three Phase
200V7.5HP (25A)
230V7.5HP (22A)
460V15HP (21A)
575V15HP (17A)
Optional Overload RelayIOL-25S

General Specifications

Contactor Frame Size25A
Rated Insulation VoltageUL/CSA: 600V
IEC/VDE 0660: 1000V
Rated Impulse Voltage
IEC60947-1
6kV
Degree of ProtectionMain Terminals: IP10
Coil Terminals: IP20
Auxiliary Terminals: IP20
Rated Operating Frequency25 to 400 Hz
Vibration Resistance
(5 to 200Hz)
Contactor Open: 4.5g
Contactor Closed at Coil: 5g
Mechanical Endurance10,000,000 (AC Coil) Operations
Electrical Endurance (AC-3)1,200,000 Operations
Shock Resistance
(1/2 Sine Wave = 11ms)
Contactor Open: 8g
Contactor Closed at Coil: 12g
SCCR5kA
Terminal Capacity
(UL /CSA)
Stranded / Solid: 1 or 2
14 - 8AWG
Power Terminals Screw DriverPhilips #2
Tightening Torque16 lb-in
Environmental ConditionsAmbient Storage Temperature: -67° to 176°F (-55° to 80°C)
Operating Ambient Temperature : -13° to 131°F (-25° to 55°C)
Climatic Withstand: According to IEC 60680-2
Pollution Degree: 3
Mounting: 35mm DIN-rail Acc. DIN EN50 022
Dimensions3.189"H x 1.772"W x 3.425"D
(81mm H x 45mm W x 87mm D)
Weight0.86 lbs
Warranty1.5 Years

Control Circuit Ratings

AC Coil Voltage Class480VAC (60Hz)
400 to 415VAC (50Hz)
Voltage Range480VAC (60Hz): 384 to 528VAC
400 to 415VAC (50Hz): 320 to 456.5VAC
Coil Operating Limits480VAC Pick-up : 192 to 364.8VAC (60Hz)
400 to 415VAC Pick-up : 160 to 315.4VAC (50Hz)
480VAC Drop-out: 120 to 312VAC (60Hz)
400 to 415VAC Drop-out: 100 to 269.75VAC (50Hz)
Coil Consumption (Single Coils)Sealed: 5.5 to 9.3VA
Inrush: 70.0VA
Heat Loss2.6W
Power FactorSealed: 0.28 Cosɸ
Inrush: 0.85 Cosɸ
Operating TimeCoil Energization-N.O. : 8 to 20ms
Coil De-energization-N.O. : 6 to 13ms

Ratings & Reviews

No reviews available

Be the first to Write a Review