MC-800A-22-AC/DC100, Contactor, 3 Pole, 100-127VAC/100-100VDC

LS Electric MetaSol Contactor 800 Amp Frame, Lug Terminals Electric, 3 Pole, 100-127VAC/100-100VDC, 2 N.O. / 2 N.C. Aux. Compatible Relay MT-800

Weight: 49.3 lbs.Made in: Korea (the Republic of)

MC-800A-22-AC/DC100, Contactor, 3 Pole, 100-127VAC/100-100VDC

LS Electric MetaSol Contactor 800 Amp Frame, Lug Terminals Electric, 3 Pole, 100-127VAC/100-100VDC, 2 N.O. / 2 N.C. Aux. Compatible Relay MT-800

Weight: 49.3 lbs.Made in: Korea (the Republic of)
Out Of Stock
$2,629.35
QuantityPrice


Discontinued, limited to stock on-hand.

Specifications

LS Electric MetaSol Contactor 800 Amp Frame, Lug Terminals Electric, 3 Pole, 100-127VAC/100-100VDC, 2 N.O. / 2 N.C. Aux. Compatible Relay MT-800

  • DIN Rail-Mountable
  • UL508 Compliant
  • Direct-Mounting Overload Relays
  • UL and CE Certified
  • RoHS Compliant
  • Auxiliary Contacts Standard

GENERAL SPECIFICATIONS

Number of Poles3
Rated Operational Voltage, Ue690V
Rated Insulation Voltage, Ui1000V
Rated Frequency60Hz
Rated Impulse Withstand Voltage, Uimp8kV
Resistive Load (AC1)900
Maximum Operations per Hour (AC3)1200
Mechanical Durability2,500,000
Electrical Durability500,000
Auxiliary Contacts (standard)2 N.O. / 2 N.C.
Conductor Size (solid) 65/75°C Cu - wire only1700 Kcmil - Busbar
RoHSCompliant
Standards UL508 File # E108780 / E206826, CE

UL HP RATINGS (AC3 MOTOR LOAD)

Three Phase200V : 200HP (552A)
230V : 300HP
460V : 600HP
575V : 600HP
Optional Overload RelayMT-800

CONTROL CIRCUIT RATINGS

Control Voltage (50/60Hz)100-240,440-500
Coil Consumption @ 20°C (220V, 60Hz)Inrush : 1,000VA
Sealed : 29VA
Coil Voltage100-127VAC / 100 - 110VDC
Operational Voltage85 - 139.7VAC / 85 - 121VDC (85 - 110%)
Drop-out Voltage30 - 76.2VAC / 30 - 66VDC (30 - 60%)

Ratings & Reviews