45018ET3GKD586/7-W22, AC Mtr, Crusher Duty, TEFC, 586/7, Footed, 3 Phase, 1800 RPM, 460V, 501 FLA, 450 HP
45018ET3GKD586/7-W22, AC Mtr, Crusher Duty, TEFC, 586/7, Footed, 3 Phase, 1800 RPM, 460V, 501 FLA, 450 HP
WEG AC Motor, NEMA Premium Efficiency, Crusher Duty, TEFC, 586/7 Frame, Cast Iron, Foot Mount, 3 Phase, 1800 RPM, 460V, 501 FLA, 450 HP
*Images are for illustrative purposes and may not represent the actual configuration of the product.
Specifications
WEG AC Motor, NEMA Premium Efficiency, Crusher Duty, TEFC, 586/7 Frame, Cast Iron, Foot Mount, 3 Phase, 1800 RPM, 460V, 501 FLA, 450 HP
*Images are for illustrative purposes and may not represent the actual configuration of the product.
- 50/60 Hz rated (380V on Nameplate – 400/415 available)
- Rated 50 Hz at same Horsepower up to 250HP 1.0 Service Factor for 2, 4 & 6 Pole motors
- Class F insulation (Impregnation Resin and Magnet wire are class H)
- NEMA design A. All ratings exceed NEMA design C torque
- F1 Mounted (F2 convertible). Frames 447T and up can easily be F2 converted by simply rotating the terminal box adapter
- Stainless Steel Nameplate – Laser etched with high contrast background
- Regreasable ball bearings
- Gasketed conduit box
- Class I, Div. 2, Groups A, B, C & D – T3, Class II, Div. 2, Groups F & G – T3C
Specifications
| Phase | Three Phase |
| Frame | 586/7T |
| Output | 450 HP |
| Poles | 04 |
| Frequency | 60 Hz |
| Rated speed | 1786 rpm |
| Slip | 0.78 % |
| Full Voltage - No Cables | 460 V |
| Rated Current | 501 A |
| LR Amperes | 3758 A |
| LRC | 7.5x(Code H) |
| No Load Current | 160 A |
| Rated Torque | 1320 ft.lb |
| Locked Rotor Torque | 240 % |
| Breakdown Torque | 250 % |
| Insulation Class | F |
| Service Factor | 1.15 |
| Moment of Inertia | - |
| Design | A |
| Locked Rotor Time | 45s (cold) 25s (hot) |
| Temperature Rise | 80 K |
| Duty Cycle | S1 |
| Maximum Room Temperature | 40 °C |
| Minimum Room Temperature | -20 °C |
| Degree of Protection | IP55 |
| Altitude | 1000 m |
| Cooling Method | TEFC Totally Enclosed Fan Cooled |
| Mounting | F-1 |
| Rotation Direction | Both |
| Noise Level | 78.0 dB(A) |
| Starting Method | Direct |
| Enclosure Material | Iron |
| Front Bearing Shielding | C3 |
| Front Bearing Size | NU-322 |
| Front Bearing Type | Roller |
| Front Sealing Type | Taconite Labyrinth |
| Rear Bearing Shielding | C3 |
| Rear Bearing Size | 6319 |
| Rear Bearing Type | Ball |
| Rear Sealing Type | No Rear Sealing |
| Grease Type | Mobil Polyrex EM |
| VFD Turndown VT | 1000:1 |
| VFD Turndown CT | 6:1 |
Application Notes
| Title | Summary | Related Links |
|---|---|---|
| AN-GEN-004 Determining Motor Full Load Amps (FLA) | How to determine your motor’s FLA. |