UTS1200N-AE0-1200, MCCB, 35KA, 3 pole, trip unit with Ammeter, Earth Leakage Protection, 600-1200A thermal range, 2400-18000A magnetic range

LS Electric Susol UT Series MCCB, UL489, 1200A Frame, 35KA Interrupt Capacity, 3 pole, Line-side and Load-side lugs, Adjustable trip unit with Ammeter, Earth Leakage Protection, 600-1200A thermal adjustable range, 2400-18000A magnetic adjustable range. This item is special order and non-cancellable, non-returnable.

Weight: 40.28 lbs.Made in: Korea (the Republic of)

UTS1200N-AE0-1200, MCCB, 35KA, 3 pole, trip unit with Ammeter, Earth Leakage Protection, 600-1200A thermal range, 2400-18000A magnetic range

LS Electric Susol UT Series MCCB, UL489, 1200A Frame, 35KA Interrupt Capacity, 3 pole, Line-side and Load-side lugs, Adjustable trip unit with Ammeter, Earth Leakage Protection, 600-1200A thermal adjustable range, 2400-18000A magnetic adjustable range. This item is special order and non-cancellable, non-returnable.

Weight: 40.28 lbs.Made in: Korea (the Republic of)
Lead Time
$3,827.85
QuantityPrice


Discontinued, limited to stock on-hand.

Specifications

LS Electric Susol UT Series MCCB, UL489, 1200A Frame, 35KA Interrupt Capacity, 3 pole, Line-side and Load-side lugs, Adjustable trip unit with Ammeter, Earth Leakage Protection, 600-1200A thermal adjustable range, 2400-18000A magnetic adjustable range. This item is special order and non-cancellable, non-returnable.

  • UL489 Listed MCCB for branch circuit protection
  • New 100 amp frame with 2 or 3 pole options
  • Digital trip unit for 800 and 1200 amp frames
  • Multiple breaking capacity choices
  • Optimal overload protection
  • 600VAC maximum rated operational voltage
  • UL File #E231289

Accessories
  • Internal electrical auxiliaries (auxiliaries, alarms)
  • Through-the-door rotary disconnect handles
  • Flange-mount disconnect handles
  • Locking devices

GENERAL SPECIFICATIONS

Frame Size (AF)1200A
Rated Amps1200A
Number of Poles3
Wire/Cable SizeAWG 3/0 - 500kcmil (4 conductor)
Rated Operational Voltage600VAC
UL Interrupting RatingN (low)
240VAC (50/60Hz)50kA
480VAC (50/60Hz)35kA
600VAC (50/60Hz)18kA
Mechanical Life (operations)2,000
Electrical Life (operations) @600VAC500
Trip Unit with AmmeterAdjustable
Thermal Adjustable Range600 - 1200A
Magnetic Adjustable Range2400 - 18,000A
Earth Leakage ProtectionYes (Except Residual Current)
StandardsUL 489
File No. E231289
Dimensions16.26"H x 8.27"W x 6.14"D
Weight40.28lbs.

Ratings & Reviews

No reviews available

Be the first to Write a Review