MC-500A-22-AC/DC200, Contactor, 3 Pole, 200-240VAC/200-220VDC
LS Electric MetaSol Contactor 800 Amp Frame, Lug Terminals Electric, 3 Pole, 200-240VAC/200-220VDC, 2 N.O. / 2 N.C. Aux. Compatible Relay MT-800
Weight: 49.3 lbs.Made in: Korea (the Republic of)
Specifications
LS Electric MetaSol Contactor 800 Amp Frame, Lug Terminals Electric, 3 Pole, 200-240VAC/200-220VDC, 2 N.O. / 2 N.C. Aux. Compatible Relay MT-800
- DIN Rail-Mountable
- UL508 Compliant
- Direct-Mounting Overload Relays
- UL and CE Certified
- RoHS Compliant
- Auxiliary Contacts Standard
GENERAL SPECIFICATIONS
| Number of Poles | 3 |
| Rated Operational Voltage, Ue | 690V |
| Rated Insulation Voltage, Ui | 1000V |
| Rated Frequency | 60Hz |
| Rated Impulse Withstand Voltage, Uimp | 8kV |
| Resistive Load (AC1) | 580 |
| Maximum Operations per Hour (AC3) | 1200 |
| Mechanical Durability | 2,500,000 |
| Electrical Durability | 500,000 |
| Auxiliary Contacts (standard) | 2 N.O. / 2 N.C. |
| Conductor Size (solid/stranded) 65/75°C Cu - wire only | 350 - 800 Kcmil |
| RoHS | Compliant |
| Standards | UL508 File # E108780 / E206826, CE |
UL HP RATINGS (AC3 MOTOR LOAD)
| Three Phase | 200V : 150HP (414A) 230V : 200HP (480A) 460V : 400HP (477A) 575V : 400HP (382A) |
| Optional Overload Relay | MT-800 |
CONTROL CIRCUIT RATINGS
| Control Voltage (50/60Hz) | 100-240,440-500 |
| Coil Consumption @ 20°C (220V, 60Hz) | Inrush : 1,000VA Sealed : 29VA |
| Coil Voltage | 200-240VAC / 200 - 220VDC |
| Operational Voltage | 170 - 264VAC / 170 - 242VDC (85 - 110%) |
| Drop-out Voltage | 60 - 144VAC / 60 - 132VDC (30 - 60%) |