MC-100A-22-AC208, Contactor, 100 Amp, 208VAC, 60Hz
LS Electric Metasol Contactor, 100 Amp, Box Lug Terminals Electric, 208VAC, 60Hz, 2 N.O. / 2 N.C. Aux., Compatible Overload Relay MT-95
Weight: 4 lbs.Made in: Korea (the Republic of)
Specifications
LS Electric Metasol Contactor, 100 Amp, Box Lug Terminals Electric, 208VAC, 60Hz, 2 N.O. / 2 N.C. Aux., Compatible Overload Relay MT-95
- DIN Rail-Mountable
- UL508 Compliant
- Direct-Mounting Overload Relays
- UL and CE Certified
- RoHS Compliant
- Auxiliary Contacts Standard
GENERAL SPECIFICATIONS
| Number of Poles | 3 |
| Rated Operational Voltage, Ue | 690V |
| Rated Insulation Voltage, Ui | 1000V |
| Rated Frequency | 60Hz |
| Rated Impulse Withstand Voltage, Uimp | 8kV |
| Resistive Load (AC1) | 160 |
| Maximum Operations per Hour (AC3) | 1800 |
| Mechanical Durability | 12,000,000 |
| Electrical Durability | 2,000,000 |
| Auxiliary Contacts (standard) | 2 N.O. / 2 N.C. |
| Conductor Size (solid/stranded) 65/75°C Cu - wire only | 8 - 00 AWG |
| RoHS | Compliant |
| Standards | UL508 File # E108780 / E206826, CE |
UL HP RATINGS (AC3 MOTOR LOAD)
| Single Phase | 115V : 10HP (100A) 230V : 20HP (56A) |
| Three Phase | 200V : 30HP (88A) 230V : 40HP (104A) 460V : 75HP (96A) 575V : 75HP (77A) |
| Optional Overload Relay | MT-95 |
CONTROL CIRCUIT RATINGS
| Control Voltage | 50Hz : 24,120,230 60Hz : 24,120,208,230,480 |
| Coil Consumption @ 20°C (220V, 60Hz) | Inrush : 216VA Sealed : 16VA |
| Coil Voltage | 208VAC |
| Operational Voltage | 176.8 - 228.8VAC (85 - 110%) |
| Drop-out Voltage | 62.4 - 124.8VAC (30 - 60%) |