G015K5QH2A04, LVGP Transformer, 15 kVA PRI: 480 V SEC: 208Y/120 V:
G015K5QH2A04, LVGP Transformer, 15 kVA PRI: 480 V SEC: 208Y/120 V:
Micron General Purpose Transformer, Group J, 15 kVA Type 3-V, PRI: 480 V SEC: 208Y/120 V: FCAN: 2-2.5% FCBN: 4-2.5% **Must Ship LTL Truck Freight**
Specifications
Micron General Purpose Transformer, Group J, 15 kVA Type 3-V, PRI: 480 V SEC: 208Y/120 V: FCAN: 2-2.5% FCBN: 4-2.5% **Must Ship LTL Truck Freight**
- Built and tested in accordance with applicable NEMA, ANSI and IEEE standards
- All 600 volt class transformers are UL listed unless otherwise noted
- Seismically tested, seismically qualified, and exceeds requirements of the Uniform Building Code (UBC) and California Code Title 24
- Designed for 60 Hz operation
- Short term overload is designed into transformers as required by ANSI: transformers will deliver 200% nameplate load for one-half hour; 150% load for one-hour; and 125% load for four-hours without being damaged provided that a constant 50% load precedes and follows the overload. See ANSI C57 .96-01.250 for additional limitations
- Primary and secondary windings are terminated in the wiring compartment
- Encapsulated units have copper leads or stabs brought out for connections, external cables rated at 90 °C (sized at 75 °C ampacity) for encapsulated designs recommended
Application Notes
| Title | Summary | Related Links |
|---|---|---|
| AN-CPT-005 Selection Guide for Single Phase LVGP Transformers | How select a single-phase LVGP Micron transformer... | |
| AN-CPT-006 Selection Guide for Three Phase LVGP Transformers | How to select a three-phase LVGP transformer... |