Micron General Purpose Transformer, Group A, 50VA, Type 1-E, Single-phase, Encapsulated, 60Hz, PRI: 240x480, SEC: 120/240V
- Built and tested in accordance with applicable NEMA, ANSI and IEEE standards
- All 600 volt class transformers are UL listed unless otherwise noted
- Seismically tested, seismically qualified, and exceeds requirements of the Uniform Building Code (UBC) and California Code Title 24
- Designed for 60 Hz operation
- Short term overload is designed into transformers as required by ANSI: transformers will deliver 200% nameplate load for one-half hour; 150% load for one-hour; and 125% load for four-hours without being damaged provided that a constant 50% load precedes and follows the overload. See ANSI C57 .96-01.250 for additional limitations
- Primary and secondary windings are terminated in the wiring compartment
- Encapsulated units have copper leads or stabs brought out for connections, external cables rated at 90°C (sized at 75°C ampacity) for encapsulated designs recommended
Insulation System Classification
| Ambient |
+ Winding Rise |
+ Hot Spot |
= Temp. Class |
| 40°C |
55°C |
10°C |
105°C |
| 40°C |
80°C |
30°C |
150°C |
| 40°C |
115°C |
30°C |
185°C |
The design life of transformers having different insulation systems is the same -the lower temperature systems are designed for the same life as the higher temperature systems.
Sound Levels All Micron 600 volt class dry-type distribution transformers are designed to meet NEMA ST-20 levels listed here.
| KVA |
NEMA Average* Sound Level in db40 |
| 0-9 |
40 |
| 10-50 |
45 |
*Applies to general purpose transformers only.